BITUMINOUS FLASHINGS | |
Specification DFE-5 |
For non load-bearing construction (alternate) [See also
DFE-1 (NLB)] GeneralThis flashing specification is an alternate detail to DFE-1 (NLB) for use
on non load-bearing construction, or where there is any potential for differential movement between the deck and the parapet or wall. The vertical wood curb should be fastened to the deck only.Note: All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual shall be considered part of this
specification.Preparation for Flashing: Any previously installed metal cap or
counterflashing must be lifted or removed, to permit application of the expansion joint cover. ApplicationBase Flashing: Refer to Flashing Specification DFE-1 (NLB) for detailed
instructions on application of the base flashing.Metal Cap Flashing: The metal flashing should be installed in accordance
with the metal manufacturers specifications and details, or in accordance with SMACNA procedures. It should overlap the base flashing a minimum of 4" (102 mm). Surfacing: DynaFlex requires no additional surfacing.
For an identical copy of this specification, ask for RS-4223.