Johns Manville  

4CND/4FND/4PND. CSI 3-Part Specifications.

jmlogo.jpg (11366 bytes)

SBS Modified Bitumen Specifications

Specification 4CND/4FND/4PND


Four Ply Hot Mopped Modified Bitumen Mineral Surfaced Roofing System. For use over plywood or other nailable decks on inclines up to 3" per foot (250 mm/m).

For Regions 1, 2 and 3

Materials per 100 sq. ft. (9.3 m 2 ) of Roof Area


Sheathing Paper:
Wood board decks only

1 layer

Felts:
Base: GlasBase, GlasBase Plus, DynaBase or PermaPly 28

Intermediate: GlasPly Premier or GlasPly IV 2 layers

1 layer

 

2 layers


Cap:
4CND�DynaKap, DynaKap FR, DynaMax or DynaMax FR

4FND�DynaGlas, DynaGlas FR or DynaGlas 30 FR

4PND�DynaLastic 180, DynaLastic 180 FR, DynaLastic 250 or

DynaLastic 250 FR

1 layer


Asphalt (Refer to Para. 7A.8): Trumbull or other JM Approved Asphalt

Incline per foot
Up to 1/2"
1/2" to 3"

Asphalt
190°F, Type III, Steep
220°F, Type IV, Special Steep

Total Weight
69 lbs. (31 kg)
69 lbs. (31 kg)

General

This specification is for use over any type of approved structural deck (without insulation) which can receive and adequately retain nails or other mechanical fasteners that may be recommended by the deck manufacturer. Examples of these decks are wood, plywood, and approved oriented strand board (OSB). This specification is not for use directly over lightweight, insulating concrete decks.

Design and installation of the deck and/or roof substrate must result in the roof draining freely, to outlets numerous enough and so located as to remove water promptly and completely. Areas where water ponds for more than 24 hours are unacceptable and will not be eligible for a JM Roofing System Guarantee.

Note: All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual shall be considered part of this specification.

Flashings

Flashing details can be found in the "Bituminous Flashings" section of the JM Commercial/Industrial Roofing Systems Manual.

Application

On roof decks with slopes up to 1/2" per foot (41.6 mm/m), the roofing felts and modified bitumen sheets may be installed either perpendicular or parallel to the roof incline.

Over wood board decks, one ply of sheathing paper must be used under the base felt, next to the deck.

Using one of the base felts listed, start with a piece 24" (610 mm) wide. The remaining felts are to be applied full width with 3" (76 mm) side and 4" (102 mm) end laps over the preceding sheets. Nail the laps at 9" (229 mm) centers, and down the longitudinal center of each felt place two rows of nails, with the rows spaced approximately 11" (279 mm) apart, and nails staggered on approximately 18" (457 mm) centers. Use nails or fasteners appropriate to the type of deck, with 1" (25 mm) minimum diameter caps. For additional fastener information, refer to the fastener data in the "Roof Decks" section of the current JM Commercial/Industrial Roofing Systems Manual.

Roll an 18" (457 mm) wide piece of one of the intermediate felts listed into a full mopping of asphalt. Over that, apply a full width piece. The remaining felts are to be applied full width, overlapping the preceding felts by 19" (483 mm), so that at least 2 plies of felt cover the base felt at all locations.

Apply a full width piece of one of the cap sheets listed into a full mopping of asphalt. Subsequent sheets are to be applied in the same manner, with 4" (102 mm) side and end laps over the preceding sheets (6" [152 mm] end laps for DynaLastic products).

Apply all felts so that they are firmly and uniformly set, without voids, into the hot asphalt. Asphalt temperature should be at the Equiviscous Temperature (EVT), ±25°F (±14°C), at the point of application. All felt edges shall be well sealed. The asphalt shall be applied just before the felt, at a nominal rate of 23 lbs. per square (1.1 kg/m2). For modified bitumen sheets, the asphalt temperature shall be at a minimum of 400°F (204°C), or at the EVT, whichever is higher, when the sheet is set into it. This higher temperature maximizes the bonding of the modified bitumen sheet.

Cap sheets with polyester reinforcement must be allowed to relax in an unrolled position prior to installation.

For cold weather application techniques, refer to Paragraph 7A.31.

Steep Slope Requirements
Special procedures are required on inclines over 1/2" per foot (41.6 mm/m). Refer to Paragraph 7A.29.

Surfacing
No additional surfacing is required.

Asphalt
Asphalt should meet the requirements of ASTM D 312.

JM Guarantees require the use of Trumbull asphalt or another JM Approved Asphalt. The Contractor must provide an Asphalt Confirmation Number (ACN) on projects which require a JM Guarantee. The ACN will indicate that the asphalt was registered with the approved asphalt source.