Excel 10 Q7750A Zone Manager. CSI 3-Part Specifications. Large file (>500kB).
|
Excel 10 |
SPECIFICATION DATA |
Features
- Interfaces Excel 5000� System C-Bus to Excel 10
- Echelon� LonWorks� (E-Bus) network.
- Provides a B-Port connection via a PC for the XI581 Operator Interface (via XI584), CARE and LiveCARE.
- User access of subsystem data via CARE programmed user defined point names.
- Energy management strategies CARE programmable.
- Control interaction strategies CARE programmable.
- Time programs CARE programmable.
- Alarm reporting for Excel 10 E-Bus network.
- Application alarm reporting.
- Full interaction with other controllers on C-Bus using global data.
GENERAL The Q7750A Excel 10 Zone Manager is a programmable master controller for an Excel 10 Subsystem. It provides energy management functions and communication interfaces between EXCEL 5000� System products and the Excel 10 Echelon� LonWorks� (E-Bus) network. The Q7750A provides C-Bus (9600 baud and 1M baud) and E-Bus (78k baud) communication interfaces. It also maps user selectable Excel 10 Subsystem data points into C-Bus points with a full set of point attributes, including user addresses.
|
DESCRIPTION There are two hardware versions of the Q7750A. 1000-series devices (with a part number suffix of 1xxx) have a twisted pair topology (TPT) E-Bus transceiver. 2000-series devices (with a part number suffix of 2xxx) have have a free topology (FTT) E-Bus tranceiver. The Q7750A is delivered with operating system software on EPROMs. The Zone Manager contains all time programs, user addresses and Excel 10 Subsystem mapping information. Mapping is the term used to describe the allocation of Excel 10 Subsystem data to Q7750A data points that are accessible from the C-Bus. This mapping process is executed using a PC-based software tool (CARE or E-Vision). |
Fig. 1. Example Q7750A Excel 10 zone manager subsystem (2000-series devices shown).
SPECIFICATIONS
System Capabilities:
Table 1. System Capabilities
Category |
Limits/Rates/Options |
Number of devices on C-Bus | Maximum of 29. |
Number of Excel 10 devices on E-Bus | Maximum of 120 (one Q7751A Router is required for each 60 Excel 10 device segment). |
Number of points supported | Maximum of 1000. |
C-Bus baud rates | 9600 baud, with XD 505 submodule option. 1M baud with XD 508 submodule option. |
Dial-up | Vial XDM506 submodule. |
LED Status Information:
Table 2. Q7750A Excel 10 Zone Manager LED Status Information.
LED No. |
Explanation |
Color | LED function if On |
LED function if Off |
1 | 5V (POWER) | Green | Power on | Power off |
2 | Contr. (RUN) | Green | Software is running, watchdog is triggered |
Watchdog locked, software not working |
3 | B-PORT (send) | Yellow | Q7750A sends data on RS232 port* |
No communication |
4 | B-PORT (receive) | Yellow | Data is sent to Q7750A on the RS232 port* |
No communication |
5 | C-Bus (send) | Yellow | Q7750A sends data on the C-Bus * |
No data sent on the C-Bus |
6 | C-Bus (receive) | Yellow | Q7750A receives data from the C-Bus * |
No data received from the C-Bus |
7 | E-Bus | Yellow | E-Bus network activity * (see NOTE) |
No E-Bus network activity |
8 | Service LED | Red | Blinking not configured | E-Bus initialized and working correctly |
NOTE: LED 7 is used to display E-Bus network activity. In
1000-series devices it flickers with data being transmitted or
received, but in 2000-series
devices it flickers only with data being received.
Communications: E-Bus: The Q7750A uses a transformer-coupled communications port with encoded data presented to controllers and devices on the E-Bus at 78K bits per second. The E-Bus is insensitive to polarity, eliminating installation errors due to miswiring. The maximum number of nodes per E-Bus is 60. With the addition of a Q7751A Router, the maximum number of nodes increases to 120 or 60 per E-Bus segment. The recommended wire for the E-Bus will level IV, 22 AWG (Belden part number 9D220150) or plenum rated Level IV, 22 AWG (Belden part number (H2201504) nonshielded, twisted pair, solid conductor wire. Honeywell E-Bus cable is available. See Installation Instructions, form number 95-7509. Additionally, Echelon approved shielded cable can be used. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables. 1000-series: 2000-series: C-Bus Mechanical: Dimensions in in. (mm) HWD:
Weight in lb (kg):
Housing Material:
Environmental Ratings:
Shipping Temperature:
Relative Humidity:
Approval Bodies: The Q7750A1xxx is listed under UL 916, File Number S4804
Protection Class: IP30.
� U.S. Registered Trademark |
Memory: Connections:
Hardware: Power Supply: Power Consumption: Battery Back-up: Mounting Options: The following accessories are available: Table 3. Accessories
|