Honeywell Inc.  

T7770A-G Wall Modules. CSI 3-Part Specifications.

T7770A,B,C,D,E,F,G, Wall Modules

Features

  • Models with setpoint adjustment.
  • Models with occupied/unoccupied override (bypass) with LED.
  • Models with 3-position (auto/0/1) or 5-position (auto/0/1/2/3   speed) fan switch.
  • Models with or without Honeywell logo.
  • E-Bus jack on all models except low cost T7770A1006, T7770A1014.
  • Locking cover on all models.
  • Operating range 45 to 99°F (7 to 37°C).
  • UL 94-5V rated.

GENERAL

The T7770A through G are a family of direct wired wall modules for use with Honeywell Excel 600, 500, 100, 80, 20, and W7750, W7751, W7752, W7753, W7761 Controllers. All models have a space temperature sensor; some models have setpoint adjustment, override with LED, and fan switch.

DESCRIPTION

The T7770A through G are a family of direct wired wall modules for use with Honeywell Excel 600, 500, 100, 80, 20, and W7750, W7751, W7752, W7753, W7761 Controllers. All models have a space temperature sensor; some models have setpoint adjustment, override with LED, and fan switch.

SPECIFICATIONS

Models:

Table 1. T7770 Wall Module Models.

Model Numbers

 

 

 

 

Honeywell Logo

No Honeywell Logo

Setpoint
Adjustment

Occupied/
Unoccupied Button and LED

Fan Switch
3 or 5 Position

Compatible With

T7770A1006

T7770A1014

Excel 600, 500,

T7770A2004

T7770A2012

100, 80, 20 and

T7770B1004

T7770B1012

55 to 85°F

Excel 10

T7770B1020

T7770B1038

10 to 35°C

W7750A,B

T7770B1046

T7770B1053

±

W7751B,D,F,H

T7770C1002

T7770C1010

55 to 85°F

X

W7752A,B,C

T7770C1028

T7770C1036

10 to 35°C

X

W7753

T7770C1044

T7770C1051

±

X

W7761

T7770D1000

T7770D1018

X

Controllers

T7770E1007

T7770E1015

55 to 85°F

X

3

 

T7770E1023

T7770E1031

10 to 35°C

X

3

 

T7770E1049

T7770E1056

±

X

3

 

T7770F1005

T7770F1013

55 to 85°F

X

5

 

T7770F1021

T7770F1039

10 to 35°C

X

5

 

T7770F1047

T7770F1054

±

X

5

 

T7770G1003

T7770G1011

X

5

 

 

NOTE: Refer to T7770A through G Installation Instructions, 95-7538, for wall module settings and wiring diagrams. Some T7770 features may not be available with all controllers.

 

Construction:

Two-piece construction, a cover and an internally wired subbase. Field wiring 14 to 22 AWG (2.0 to 0.34 mm2) connects to a terminal block in the subbase. The wall module is activated by plugging into the prewired subbase.

Temperature Sensor Operating Range:

45 to 99°F (10 to 37.2°C).

Temperature Sensor Accuracy

T7770A-G 20K Ohm Nonlinearized Sensor:

All T7770 models are furnished with a 20K Ohm nonlinear NTC temperature sensor that follows a specific temperature-resistance curve. See Fig. 1. Honeywell controllers used with the T7770 employ an algorithm that provides readings close to the actual temperature. Table 2 summarizes the T7770 nonlinearized sensor accuracy for normal operating temperatures. Across the range of 41 to 99°F (5 to 37°C) the accuracy is better than ± 0.75°F (±0.42°C).

 

Fig. 1. Temperature verses resistance for nonlinear sensor.

 

Table 2. Nonlinear Temperature Sensor Accuracy.

Ambient Temperature
°F (°C)

Maximum Error
°F (°C)

Minimum Error
°F (°C)

Nominal Resistance
(Ohms)

60 to 64
(15.56 to 17.78)

±0.52 (±0.29)

0 (0)

31543

65 to 69
(18.33 to 20.56)

±0.49 (±0.27)

0 (0)

27511

70 to 77
(21.11 to 25.00)

±0.48 (±0.27)

0 (0)

24047 to 19989

78 to 80
(25.65 to 26.67)

±0.49 (±0.27)

0 (0)

18490

81 to 85
(27.22 to 29.44)

±0.52 (±0.29)

0 (0)

16264

 

Communications:

Except for the T7770A1006, T7770A1014 models, T7770s all have an E-Bus communications port. If needed, the jack plug must be removed in the field, and terminals 1 and 2 wired according to the installation instructions. E-Bus communication is not applicable when the wall modules are used with Excel 600/500/100/80/20 Controllers. The E-Bus is insensitive to polarity, minimizing installation errors due to miswiring.

The recommended wire size for the E-Bus is Level IV, 22 AWG (0.34 mm2) plenum or non-plenum rated, nonshielded, twisted pair, solid conductor wire.

 

T7770B,C,E,F Setpoint Adjustment:

For Wall Modules with a setpoint adjustment, the controller must be programmed for the values in Table 3.

 

Table 3. Setpoint Values.

Setpoint Value

Program Setting

55°F

2.773V

65°F

2.148V

75°F

1.345V

85°F

0.43V

 

T7770C,D,E,F, and G Wall Module Bypass Override /LED Operation

When Used With Excel 10 Controllers:

The controller provides timed occupied and unoccupied temperature setpoints for the Wall Module, see Fig. 2. The bypass pushbutton is used to change the controller into the modes shown in Table 4 and Fig. 3. The override LED displays the override status of the controller.

Fig. 2. LED and bypass pushbutton locations.

 

 

Table 4. Wall Module Operation.

Pushbutton
Held Down

Controller
Mode


LED Status

0 to 1 second

No override.

Off

1 to 4 seconds

Timed occupied override.

On

4 to 7 seconds

Unoccupied override.

Single blink per second

Longer than 7 seconds

No override.

Off

Continuous occupied overridea.

Two blinks per second

 aRemote function. Generated from the network.

When Used With Excel 600/500/100/80/20 Controllers:

All Excel 600/500/100/80/20 Controllers are fully programmable. The application engineer-programmer can program the override and LED to operate in any manner desired. The override (bypass) input is a dry contact, normally open, momentary digital input when the wall module does not have a fan switch. When a fan speed switch (basically a series of resistances based on fan switch position) is present, the bypass button is an analog input. See the Table 5 for those resistances.

Fig. 3. Bypass pushbutton operation.

T7770E,F,G Wall Module Fan Switch

When Used With Excel 10 FCU Controller:

With the switch in the far left position, the fan will automatically run at the speed determined by the controllers temperature control algorithm. With the switch in the 0 position, the fan is off. Position 1 is fan speed 1, etc. The fan speed switch on the wall module overrides the temperature control algorithm.

 

When Used With Excel 600/500/100/80/20 Controllers:

All the Excel 600/500/100/80/20 Controllers are fully programmable and can be programmed so that the fan speed switch and bypass button function the way that the application engineer/programmer wants. The resistances used for programming the controller are shown in Table 5.

 

Table 5. Program Settings For Wall Modules with
Fan Switch.

For Switch Position

Resistance (ohms)

Auto

11.861K ±119

0

12.686K ±127

1

13.866K ±139

2

13.04K ±130

3

14.60K ±146

Bypass button closed

10K ±100

Mounting Options:

The T7770 can be mounted on a standard two by four inch junction box or on a 60 mm diameter junction box. The subbase also provides the slotted hole pattern for the T7412 Wall Module series individual room control devices.

Dimensions (H/W/D):

5-1/32 x 3-5/32 x 1 In. (128 x 80 x 25 mm).

Environmental Ratings:

Operating Temperature: 45° to 99°F (7.2° to 37.2°C).

Shipping Temperature: -40° to 150°F (-40° to 65°C).

Relative Humidity:

5% to 95% noncondensing.

Approvals:

NEC Class II.

Energy Management Standard: UL 916.

CSA.