Excel Access Control Supervisor Pages 4-6. CSI 3-Part Specifications.
Excel Access Control Supervisor
Full Management Reporting Capability:
Access Control provides a number of status reports, database listings, and historical
logs. Status reports indicate current condition of doors/elevators, lists all card holders
"in" each building area, and can highlight on a graphic the areas to which a
card holder is assigned. Database listings provide setup information for doors, elevators,
schedules, floor groupings, building areas, and card holder data.
Historical logs include:
Valid Transactions LogFor valid door transactions, outputs card number and identification information, reader location, and date and time of access.
Audit Trail LogIdentifies the files which have been changed by an operator.
Access Commands LogProvides a listing of all commands issued to a door or area by an operator.
Access Alarms LogProvides a listing of all door/reader locations that indicated an alarm condition.
Antipassback Control LogLists antipassback activities performed by operators.
Users determine which records are to be included in historical logs and whether to print or just display the output.
Multiple Card Technologies to Fit Specific
Applications:
A variety of card reader types and styles are available for use with Access Control.
Card reader technologies include magnetic stripe, barium ferrite, Wiegand, and proximity.
To accommodate building materials, applications, and building decor, the card readers are
available in insertion, swipe, turnstile, and SENSORKEY styles. For added security,
Personal Identification Number (PIN) Pads integral with or located next to the readers are
available. PIN Pads allow for entry of user-defined access codes. In addition, when using
special access codes, PIN Pads can notify the Graphic Central operator that entry is under
duress.
Distributed Database Provides Full
Stand-Alone Operation:
If AMCs lose communication with the Graphic Central, the AMCs can use their existing
data files to continue making access decisions. Once communication is reestablished, the
AMC requests current data for all respective cards and sends the transaction information
to Graphic Central. An AMC can retain up to 1000 transactions.
System Integration of Access Control, Fire
Alarm, Building Controls, and Energy Management:
An Excel Building Supervisor Integrated can also support R7044 Excel Plus
Controllers for energy management and HVAC control and FS90 Fire & Security Systems
for fire alarm control. With a fully integrated system, Excel Building Supervisor
Integrated can coordinate and control overall building functions. For example, to
accommodate off-hour cleaning personnel, Excel Building Supervisor Integrated can
coordinate Access Control and a lighting control program to simultaneously permit access
and temporarily light a particular area.
SENSORKEY is a trademark of Sensor Engineering Co.
SPECIFICATIONS
System Capacities:
Up to 29 AMCs per F&S bus
Up to 16,000 cards per system
Up to 8 readers (with or without keypad) per AMC (up to 2 AR Reader Interface Boards per
AMC, up to 4 readers per AR Board)
240 Areas maximum
240 Elevators maximum
96 Floors maximum
250 Schedules with 8 day/time periods maximum
250 Floor groupings, each with an 8 day/time period schedule
Response time: 1 sec per card in AMC data file
Personal Computer
Hardware:
W7052/3 Gateway with F&S bus(es).
See W7052B-G Gateway Specification Data Sheet 74-2926 and W7053A-G Gateway Specification Data Sheet 74-2927 for more details.
Software:
MS-DOS 3.3 by Microsoft Corporation
Microsoft Windows Ver. 3.0
DOS SQLBase Single-User/Run software from Gupta Technologies Inc. (called
"DBWindows" on screen)
Excel by Microsoft Corporation
Micrografx Designer
S999 DeltaNet Access Control Operating System
S985 DeltaNet Graphic Central
Operating System
S979 Coprocessor Board EPROM
S980 PC Communication Board
EPROM (one per board)
S1002 Remote Terminal
S1014 LAN
Access Management Controller
Function Boards:
Power Requirements:
Power Supply/Charger
14505148-001:
Input 120V ac, +10%, -15%, 50/60 Hz
28V dc output
2A max in supervision
4A max in alarm/recharge
Power Supply Cable 14505145
Batteries:
24V dc, float-charged from power supply/charger
Environmental Limits:
Operating: 32 to 120F (0 to 49C), 5 to 95% rh noncondensing
Enclosure:
Mounting:
Surface or semiflush
Dimensions:
Single enclosure: 24 in. (610 mm) high x 22-1/4 in. (565 mm) wide x 7-3/4 in. (197 mm)
deep
Double enclosure: 38 in. (965 mm) high x 22-1/4 in. (566 mm) wide x 7-3/4 in. (197 mm)
deep
Shipping Weight:
Motherboard: 25 lb (1.1 kg)
Power supply: 8 lb (3.6 kg)
Enclosures:
Single 23 lb (10.4 kg)
Double 31 lb (14.1 kg)
Enclosure Door:
Single 8 lb (3.6 kg)
Double 12 lb (5.4 kg)
Batteries:
14506056-001 (two for 6.5 Ah): 5.7 lb (2.6 kg)
14506056-002 (two for 26 Ah): 18.7 lb (8.5 kg)
Door Strike Control:
AR Reader Interface Board: Provides 24V nominal (19 to 30V) power for door strike control
DA/DC Accessory Relay Board: Switches up to 2A and 30V max for controlling door strike
Control Relay Assembly 14505172: For door strike control using 120V ac
Door strikes can be normally energized or de-energized
Wiring:
Wiring to card reader must be within 500 ft (152m), 18 to 22 AWG (0.8 to 0.3 sq mm)
Door strike wiring: Must be within 500 ft (152m) from AMC, 14 AWG (2.1 sq mm) max
Request-to-Exit wiring: 500 ft (152m), 14 AWG (2.1 sq mm) twisted pair
Accessories:
- Card Readers
- Door Strikes
- Request-to-Exit Switches (n.o. or n.c.)
- Motherboard-to-Motherboard Cable for inside enclosure 14505154-001
- Motherboard-to-Motherboard Cable for between enclosures 14505154-002
- Legend Cards 14505149
- Lightning Protectors 14502412
- Tamper Switch 14505154
Card Reader Technologies:
Magnetic Stripe
Barium Ferrite
Wiegand
Proximity
PIN Pad
Software Licensing:
Before software delivery, the end user must execute a software license agreement.
Approvals:
UL 294, 864, and 1076
Helping You Control Your World Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, Minnesota 55408-0524 Honeywell
Latin American Region Home Building Control Honeywell Europe S.A. Honeywell Asia Pacific Inc. |
Copyright � 1994 Honeywell Inc. All Rights Reserved Rev. 4-94 |