Excel 10 Unit Ventilator Controller. CSI 3-Part Specifications.

63_9037a.gif (962 bytes)

Comfort from Experience.

Excel 10 Unit Ventilator Controller

The only solution you need for cost-effective control of unit ventilators

63_9037b.gif (1897 bytes)

 

Specifying a controller for any standard unit ventilator has never been easier with Honeywell’s Excel 10 Unit Ventilator (UV) Controller. The affordable UV Controller features a flexible design that supports all standard unit ventilator applications, keeping estimating, procurement and engineering time to a minimum. Its single zone direct digital ventilation control is proven and precise, ensuring trouble-free installation and optimum UV operation.

Honeywell UV Controllers play a key role in the
Excel 5000 � System. They may also be used in standalone applications.

A single model uses preprogrammed heating, cooling, economizer, and ASHRAE cycles I, II or III algorithms to control unit ventilators with staged, floating or pulse width modulation. When used with the Excel 10 Zone Manager or other Excel 5000 controllers and a centrally-located Excel Building Supervisor,the UV Controller provides an excellent, low-cost control solution for small to large commercial buildings.

63_9037d.gif (46370 bytes)
63_9037c.gif (1846 bytes) The open system advantage

The UV Controller uses the standard Echelon LonMark Unit Ventilator functional profile for openness and interoperability with third party LonMark devices.

Installation flexibility
New extended operating temperature rating (-40� to +150� F) ensures worry-free operation even in extreme hot or cold environments, regardless of installation site.

Energy-saving and IAQ options
Smart options put you in control of energy savings and indoor air quality. Maximize your energy savings with automatic space temperature setpoint reset. Introduce fresh outside air for improved indoor air quality by resetting the economizer minimum position.

 

Excel 10 Unit Ventilator Controller Highlights

The Excel 10 Unit Ventilator Controller is a configurable direct digital controller for all standard unit ventilator applications. All Excel 10 controllers are part of the EXCEL 5000 � System of integrated building control products and software. They are supported by the Excel Building Supervisor front-end software package, providing easy-to-use building control with a single, global platform. Because they reside on the Echelon � LonTalk � network, the controllers fit perfectly in Honeywell’s worldwide architecture and interoperate with third party LonMark � -compliant devices.

EXCEL 5000 System   Architecture

Operator Interfaces
Excel Building Supervisor
Excel XI581/2

Primary Controllers
Excel 500
Excel 100
Excel 80
Excel 20
Excel W7600
Excel OpenLINK

Zone Controllers
Excel 10
Excel W7620

63_9037e.gif (21791 bytes)

Applications Supported

W7753A Unit Ventilator Controller (8 triac outputs)

  • UVs with up to two stages heat/cool
  • UVs with floating heat/cool/economizer
  • UVs with pulse width modulating (PWM) heat/cool/economizer
  • ASHRAE Cycles I, II, and III
  • Two unused digital outputs can be used as free points controlled by the network for lighting, exhaust fans.

Optional features

  • Indoor air quality control using an external sensor/controller and economizer minimum position reset
  • Energy-saving setpoints for heating/cooling in occupied/unoccupied and standby modes
  • Control sequence shut down via window/door open digital input

Controller Hardware

Excel 10 UV Controllers are powered by standard, off-the-shelf 24 VAC power. The hardware is rated for extended temperature operation from -40� to +150� F.

The controller includes:

  • 14 AWG maximum wire size terminals for soft field wiring
  • On-board network jacks for quick commissioning and troubleshooting using the E-Vision configuration tool
  • On-board status LED confirms normal functioning at a glance
  • UL94-5V flame-retardant construction

Input/Output Data

W7753A UV Controller

Inputs

  • 1 T7770 wall module connection with space temperature sensor, setpoint, bypass button and bypass LED indicator
  • 2 resistive inputs. Options: discharge air, outdoor air, return air or mixed air temperature, fan speed switch.
  • 2 voltage/current inputs 1-10 VDC, 4-20 mA; Options: return air humidity or enthalpy, outdoor air humidity or enthalpy, filter static pressure differential, space, C0 2 , outdoor or generic sensor.
  • 4 digital inputs. Options: occupancy sensor, proof of airflow, IAQ override, smoke monitor, dirty filter, shutdown switch, window/door open, monitor switch, freeze stat, heat/cool aquastat, drip pan full.

Outputs

  • 8 triac outputs rated at 24 VAC at 500 mA maximum. Options: Cool 1-2, Heat 1-2, floating heat +/-, floating cool +/-, reversing valve, fan, packaged or floating economizer, PWM heat/cool/economizer, occupancy status, two network controlled free points.
  • 1 22 VDC, 50 mA output for sensor power

 

Network Communication

  • Standard Echelon � LonMark Unit Ventilator functional profile
  • High-performance 78K Baud communication
  • Free topology transceiver (FTT) for flexible installation
63_9037f.gif (765 bytes) 63_9037g.gif (1231 bytes)

63_9037h.gif (1478 bytes)


Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524
Home and Building Control
Honeywell Limited-Honeywell Limit�e
740 Ellesmere Road Scarborough, Ontario
MIP 2V9
Helping You Control Your World