W7600A-F Network Compatible Control Modules. CSI 3-Part Specifications. Large file (>500kB).
Honeywell W760OA-F
Network Compatible Control Modules
The W760OA-F Network Compatible Control Modules provide analog/digital inputs and outputs and interchangeable application specific control firmware that can be used in various HVAC applications. The network compatible W7600 has the ability to communicate with other network compatible W7600 modules, Q7640 Network Interface Unit, W7600G, H Building DDC and W7620 Zone Controls and a two-wire bus. Remote communication is provided through the Q7640 Network Interface Unit, an external modem and standard telephone lines. Additional components used with the W60OA-F Control Modules include W7601A, B Expansion Modules, S7600A, B Network Compatible Keyboard Display Module and R7600A Relay Modules. All components are designed for easy panel mounting.
Easily configured through a personal computer and 2M7601 Configuration Tool Software or ZM7603 Remote Monitoring Software.
Easy to use, on-site, password-protected, menu-driven, Network Compatible S7600A Keyboard Display Module to change setpoints, change time schedules, acknowledge and review alarms, and review point information.
Automated remote reporting through a personal computer and ZM7603 Remote Monitoring Software.
12-hour (AM, PM) or 24-hour (military) time-based clock with battery backup.
Industry standard inputs and outputs allow use of a wide variety of Honeywell resistance (0-4600 ohms), voltage (0-11 Vdc), and current (0-21.2 mA) sensors, and voltage (0-15 Vdc) and current (0-21.2 mA) controlled devices.
Extensive alarm-n and failure reporting.
Available in standard models for indoor applications and extended temperature models for outdoor and rooftop applications.
All standard models provide:
-8 analog inputs.
-8 digital inputs.·W7600A and W7600D (extended temperature) provide:
-4 analog outputs.
-8 digital outputs.W7600B and W7600E (extended temperature) provide:
-S analog outputs.
-8 digital outputs.W7600C and W760OF (extended temperature) provide:
-16 digital outputs.Additional inputs and outputs can be obtained with W7601A or W7601B expansion modules.
Uses interchangeable PM7600 Program Module for varying control applications.
Includes quick connect pin and socket wiring terminations on analog/digital inputs and outputs.
Provides cover labeled with detailed information for easy terminal identification.
Specifications
MODELS:
Normal Temperature Range |
Extended Temperature Range |
Input/Output |
W7600A |
W7600D |
8 analog inputs |
W7600B |
W7600E |
8 analog inputs |
W7600C |
W760OF |
8 analog inputs |
ELECTRICAL RATINGS:
Power Supply: 20-30 Vac, 50/60 Hz.
Power Consumption: 24 VA maximum-n at 30 Vac, 18 VA nominal at 24 Vac.
Output on Terminal Labeled VUR(+): 23 -41 Vdc.
Output on Terminal Labeled 20 Vdc (+): 20.0 ±l Vdc.
Maximum Current Draw: Terminal labeled VUR(+) = 80 mA. Terminal labeled 20 Vdc(+) = 160 mA (including analog outputs).
INPUT/OUTPUT:
Analog Inputs: 0-4600 ohms resistive.
0- 1 1 Vdc (51 kohm input impedance).
0-21 mA (using external resistor).
Resistance Added, No. 22 AWG Wire from Analog Input to
Sensor: 16.1 ohms/500 fe4 32.3 ohms/1000 feet.
NOTE: No. 22 AWG wire must be connected to Honeywell insulation displacement connectors.
Digital Inputs: Dry (no voltage) contact inputs (W7600 provides 12-23 Vdc across open contacts, 2-4 mA current less than .5 Vdc through shorted contacts).
Digital Outputs: Use in conjunction with the R7600A Relay Module.
4mA: ON (nominal using only R7600, 2341 Vdc open circuit voltage).
I mA: OFF (nominal using only R7600).Analog Outputs:
Current: 0-21.2 mA into a 0-750 ohm load.
Voltage: 0-15 Vdc across 1-750 ohm external resistor
Resolution: 6 bit; 0.33 mA/bit.Accuracy: 3 percent full scale.
ACCURACY:
Real-Time Clock Crystal: ±l minute/month at 771 F [251 C], ±5 minutes/month over 32' to 100' F [O' to 38' C].
Clock (50/60 Hz Selected): Line accuracy ±l second/month.
Power Outage: ±l second per changeover from 50/60 Hz to RTC.
UNDERWRITERS LABORATORIES INC. COMPONENT RECOGNIZED: UL916. CANADIAN STANDARDS ASSOCIATION CERTIFIED:C22.2, No. 205.
FEDERAL COMMUNICATIONS COMMISSION: Part 15, Class A.
BACKUP:
Clock, Power Outage:Two-day minimum (30 minutes minimum required to recharge the backup device).
User Program: Approximately ten years.
MOUNTING: Four no. 8 sheet metal screws (not provided)
DIMENSIONS: See Fig. 1.
SHIPPING WEIGHT: 3.7 pounds (1.7 kg).
HUMIDITY: 5-90 percent at 90' F [32' C] noncondensing.
TEMPERATURE RATINGS:
Ambient: W7600A,B,C: 320 to 1000 F [00 to 380 C].
W7600D,E, F: -400 to +1500 F [-400 C to +660 C].
Shipping: W760OA-F: 200 to 1200 F [-290 to 490 C].
Fig. 1-Approximate W760OA-F dimensions in in. [mm].
Helping You Control Your World
Home and Building Control |
Honeywell Latin American Region 480 Sawgrass Corporate
Parkway |
Honeywell Limited - Honeywell Limitée 155 Gordon Baker Road M2H 3N7 |
Honeywell Europe S.A. |
Honeywell Asia Pacific Inc. Room 3213-3225 |