Infloor Sales and Service  

Radiant Floor Heating. CSI 3-Part Specifications.

SECTION 15800
Heat Transfer Units
Common-Black; BPEX-Gold; PEX-Red;

RECOMMENDED SPECIFICATION FOR INFLOOR® HEATING SYSTEMS HIGH CAPACITY COMPONENTS AS THE EQUIPMENT FOR RADIANT FLOOR HEATING 

PART 1 GENERAL

1.01 SUMMARY

A.  Conditions of the Contract: The Conditions of the contract (General, Supplementary and other Conditions) and the General Requirements (sections of Division 1) govern the provisions of this section. The articles contained in this section may modify, delete or add to the provisions of the Conditions of the Contract.

1.02 SECTION INCLUDES

A. Infloor High Capacity components
B. Infloor tubing
C. System controls
D. Primary boiler loop and circulating pump
E. System treatment

1.03 SUBMITTALS

A. Product Data: Provide for manufactured products and assemblies including installation recommendations and rough-in dimensions.

B. Operating and Maintenance Instructions: Include manufacturer's descriptive literature, operating instructions, maintenance and repair data, and parts description.

1.04 WARRANTY

A. Provide twenty-five (25) year manufacturer's warranty for Infloor tubing, ten (10) year manufacturer's warranty for manifold body, and one (1) year manufacturer's warranty for other Infloor components.

1.05 QUALITY ASSURANCE

A. Installer's qualifications: Installation of Infloor Heating system shall be by a trained Infloor dealer authorized by the MAXXON� Corporation. 

B. Pressure Test: Provide hydrostatic test of primary loop, manifolds, and tubing to 100 psi (689.5 kPa) for 30 minutes. The Infloor High Capacity components are rated for 100 psi (689.5 kPa), -40 to 200 degrees F (-40 to 93.3 degrees C) operational.

1.06 DELIVERY AND STORAGE HANDLING

A. General Requirements: Materials shall be delivered in their original, unopened packages, and protected from exposure to the elements. Damaged or deteriorated materials shall be removed from the premises.

PART 2 PRODUCTS

2.01 MATERIALS

A. Infloor High Capacity components: Furnish and install a complete radiant heating panel distribution system that includes temperature gauges on supply and return manifold modules, contaminant screen and flow indicators on supply modules, 1" stainless steel isolation ball valve on supply and return modules with balancing adjustment for each circuit, and a module CV rating of 14.4 or greater. Balance each circuit to maintain even temperature drop in loops. Infloor High Capacity components to be furnished by MAXXON Corporation, Hamel, MN.

B. Infloor tubing: Radiant tubing shall be _____________________. Tubing to be furnished by MAXXON Corporation, Hamel, MN, and is to be installed in complete accord to manufacturer's instructions. Choose one of the following:

  1. Infloor barrier cross-linked polyethylene (BPEX) as provided by MAXXON Corporation, Hamel, MN: nominal 1/2" (inch) [13 mm] inside diameter with a nominal 5/8" (inch) [16 mm] outside diameter with a wall thickness of 0.059" (inch) [1.5 mm], rated for 100 psi (689.5 kPa) at 180 degrees F (82.2 degrees C) with an external ethylene vinyl alcohol (EVOH) oxygen diffusion barrier allowing no more than 0.1 gram per cubic meter per day (0.1g/m3/d). Individual circuit length to be up to 450' (feet) [137.2 m] maximum.
  2. Infloor barrier cross-linked polyethylene (BPEX) as provided by MAXXON Corporation, Hamel, MN: nominal 3/4" (inch) [19 mm] inside diameter with a nominal 1" (inch) [25 mm] outside diameter with a wall thickness of 0.059" (inch) [1.5 mm], rated for 100 psi (689.5 kPa) at 180 degrees F (82.2 degrees C) with an external ethylene vinyl alcohol (EVOH) oxygen diffusion barrier allowing no more than 0.1 gram per cubic meter per day (o.1g/m3/d). Individual circuit length to be up to 1000' (feet) [304.8 m] maximum.
  3. Infloor cross-linked polyethylene (PEX) as provided by MAXXON Corporation, Hamel, MN: nominal 1/2" (inch) [13 mm] inside diameter with a nominal 5/8" (inch) [16 mm] outside diameter with a wall thickness of 0.059" (inch) [1.5 mm], rated for 100 psi (689.5 kPa) at 180 degrees F (82.2 degrees C). Individual circuit length to be up to 450' (feet) [137.2 m] maximum.
  4. Infloor cross-linked polyethylene (PEX) as provided by MAXXON Corporation, Hamel, MN: nominal 3/4" (inch) [19mm] inside diameter with a nominal 3/4" (inch) [19 mm] inside diameter with a nominal 1" (inch) [25 mm] outside diameter with a wall thickness of 0.118" (inch) [3.0 mm], rated for 100 psi (689.5 kPa) at 180 degrees F (82.2 degrees C). Individual circuit length to be up to 1000' (feet) [304.8 m] maximum.

C. System Controls: space temperature to be maintained by using floor sensor and outdoor sensor connected to reset controller. Reset controller shall operate circulating pump(s) and boiler to maintain slab temperature in relation to changes in outdoor temperature. When used with a non-condensing boiler, a tempering valve shall be used to maintain the secondary loop delivery water temperature. Consult the Infloor Design and Installation Guide as provided by MAXXON Corporation, Hamel, MN.

D. Primary boiler loop and circulating pump: Primary circulating loop shall be supplied by others with sufficient system water flow to provide boiler supply temperature between 140 degrees F (60.0 degrees C) to 180 degrees F (82.2 degrees C) with a 20 degree F (11 degree C) maximum temperature drop between primary loop supply and return piping for non-condensing boilers, or design delivery water temperature for condensing boilers.

E. System Treatment: Install _________________________ (Choose one of the following: Formula 10�, or Infloor System Treatment.)

  1. Formula 10, a silicate-based corrosion inhibitor in concentration of one (1) quart [0.95 liter] treatment per fifty (50) gallons [190 liters] water as provided by MAXXON Corporation, Hamel, MN. NOTE: Not to be used with glycol additives.
  2. Infloor system treatment, a borate-nitrite corrosion inhibitor in concentration of 1400 ppm (one [1] quart {0.95 liter} treatment per twenty-five [25] gallons {95 liters} water) as provided by MAXXON Corporation, Hamel, MN.

END OF SECTION