Exterior Cement Board Systems (DUROCK). CSI 3-Part Specifications.
SECTION 07480
DUROCK EXTERIOR CEMENT BOARD SYSTEMS
*****************************************************************
Use this guide specification to specify DUROCK Brand Exterior
Cement Board systems by U.S. Gypsum Co. Review a copy of USG
publication SA-700 before editing specification.
*****************************************************************
PART 1 - GENERAL
GENERAL DOCUMENTS
General and Supplementary Conditions of Contract as well as
Drawings and general provisions of Contract and Division 1
Specification section, apply to work of this section.
*****************************************************************
VERSATILE DUROCK EXTERIOR CEMENT BOARDS CAN BE USED WITH A WIDE
RANGE OF CONSTRUCTION MATERIALS, METHODS, AND FINISHES. EDIT
BELOW TO DESCRIBE SCOPE OF THIS SECTION AND TO COORDINATE WITH
OTHER SECTIONS.
*****************************************************************
This Section includes exterior wall systems constructed of cement
board building panels and related materials, including:
Light gage steel framing.
Exterior finish.
Setting and grouting materials for ceramic tile and thin brick
veneer.
Insulation.
Water barrier membrane.
*****************************************************************
GENERAL REQUIREMENTS FOR THIN BRICK, SUCH AS TYPE, SIZE, AND
COLOR, CAN BE SPECIFIED IN THIS SECTION OR IN DIVISION 4. BUT TO
ASSURE COMPATIBILITY WITH DUROCK CEMENT BOARD, INSTALLATION
MATERIALS AND METHODS SHOULD BE SPECIFIED IN THIS SECTION.
*****************************************************************
Thin brick veneer is specified in Division 4 Section "Unit
Masonry".
*****************************************************************
WHENEVER POSSIBLE, STEEL FRAMING FOR CEMENT BOARD BUILDING PANELS
SHOULD BE SPECIFIED IN SAME SECTION AS BUILDING PANELS TO ASSURE
SYSTEM COORDINATION. SEE USG PRODUCT LITERATURE FOR STEEL
FRAMING SYSTEMS.
*****************************************************************
Light gage steel framing is specified in Division 5 Section
"Cold-Formed Metal Framing".
Wood framing is specified in Division 6 Section "Rough
Carpentry".
*****************************************************************
FIRE SAFING MAY BE REQUIRED BETWEEN EDGES OF FLOOR SLABS AND
CURTAIN WALL TYPE CONSTRUCTION. FOR ADDITIONAL INFORMATION, SEE
USG PRODUCT LITERATURE FOR THERMAFIBER FIRE SAFING INSULATION.
*****************************************************************
Fire safing insulation is specified in Division 7.
Flashings are specified in Division 7 Section "Flashing and Sheet
Metal".
Sealants for joints in wall system and perimeter sealing are
specified in Division 7 Section "Joint Sealers".
*****************************************************************
VERIFY SUBSTRATE REQUIREMENTS WITH AGGREGATE COATING
MANUFACTURER.
*****************************************************************
Stone aggregate in epoxy matrix is specified in Division 9
Section "Aggregate Coatings".
*****************************************************************
SEE USG PRODUCT LITERATURE FOR COMPATIBLE DRYWALL PRODUCTS.
*****************************************************************
Gypsum drywall for interior finishes of exterior walls is
specified in Division 9 Section "Gypsum Drywall".
*****************************************************************
GENERAL REQUIREMENTS FOR TILE, SUCH AS TYPE, SIZE, AND COLOR, CAN
BE SPECIFIED IN THIS SECTION OR DIVISION 9. BUT TO ASSURE
COMPATIBILITY WITH DUROCK CEMENT BOARD, INSTALLATION MATERIALS
AND METHODS SHOULD BE SPECIFIED IN THIS SECTION. SEE USG PRODUCT
LITERATURE FOR DURABOND TILE SETTING AND GROUTING PRODUCTS WHICH
ARE COMPATIBLE WITH MATERIALS SPECIFIED IN THIS SECTION.
*****************************************************************
Ceramic tile veneer is specified in Division 9 Section
"Tile".
QUALITY ASSURANCE
*****************************************************************
DELETE OR MODIFY FIRE-RESISTANCE RATING AS REQUIRED FOR PROJECT.
OTHER APPLICABLE UL DESIGNS INCLUDE U457, U458, U459, U473 and
U474. EDIT SECTION TO CONFORM TO SELECTED UL DESIGN
REQUIREMENTS.
*****************************************************************
Fire-Resistance Rating: As indicated by reference to design
designation in UL "Fire Resistance Directory"; tested per ASTM E
119.
Steel Framing: UL Design U442.
Wood Framing: UL Design U329.
*****************************************************************
USG CAN NOT ACCEPT RESPONSIBILITY FOR PERFORMANCE OF DUROCK
EXTERIOR CEMENT BOARD OR OTHER DUROCK COMPONENTS WHEN USED WITH
PRODUCTS WHICH HAVE NOT BEEN TESTED AND APPROVED BY UNITED STATES
GYPSUM COMPANY AS PART OF THE DUROCK EXTERIOR CEMENT BOARD
SYSTEM.
*****************************************************************
Unit Responsibility: Obtain panel system components from a
single manufacturer, or from manufacturers recommended by the
prime manufacturer of cement boards.
SUBMITTALS
Product Data: Submit manufacturer's product literature,
specifications, and installation instructions for each type of
component specified, including other data as may be required to
show compliance with these specifications.
Samples: Submit samples as listed below.
*****************************************************************
EDIT BELOW TO SUIT PROJECT.
*****************************************************************
Cement Board: 12 x 12 inches, apply exterior finish to one side
in color and texture required.
Metal Framing: 12 inches length, each type.
Fastener: Each type.
Reinforcing Tape: 12 inches length.
Membrane: 12 x 12 inches.
*****************************************************************
EDIT BELOW AS REQUIRED. DELETE IF COLORS ARE PRESELECTED AND
SCHEDULED.
*****************************************************************
Grout Samples for Initial Selection Purposes: Submit samples of
grout and exterior finish showing full range of colors
available.
*****************************************************************
RETAIN BELOW IF REQUIRED TO COORDINATE WITH TILE SUBMITTAL
REQUIREMENTS.
*****************************************************************
Grout Samples for Verification Purposes: Submit samples of grout
applied to tile sample boards specified in Division 9 Section
"Tile".
*****************************************************************
SPECIFY ASSEMBLY SAMPLE ONLY IF REQUIRED BY SPECIAL CONDITIONS.
*****************************************************************
Assembly: Provide 2 x 2 feet sample of assembled panel system,
containing all component materials as specified in this section
and representative veneer and finish applications as specified
for the completed system; cut-away construction to illustrate
construction and attachments.
*****************************************************************
DELETE BELOW IF NOT REQUIRED
*****************************************************************
Certification for Fire Test Performance: Submit manufacturer's
fire test report or written certification that assembly systems
have been tested by an independent laboratory and comply with
required fire test performance.
DELIVERY, STORAGE AND HANDLING
Deliver materials in original unopened packages, containers, or
bundles bearing brand name and identification of manufacturer or
supplier.
Store materials in an enclosed shelter in manner to keep them
dry, protected from weather, surface contamination, and damage
from construction traffic and other causes. Neatly stack cement
boards flat to prevent sagging. Protect emulsion products from
freezing.
Handle cement boards to prevent damage to edges, ends or sur-
faces. Protect metal framing members from being bent or damaged.
If gypsum boards are utilized, handle and store similar to cement
boards.
PROJECT CONDITIONS
Environmental Requirements, General: Comply with requirements of
referenced products application standards and recommendations of
manufacturer, for environmental conditions before, during and
after application of materials.
Weather Protection: Do not apply finishes to exterior cement
board if surface is wet, frozen, or contains frost; or when
ambient temperature is below 45 deg F (13 deg C). For at least
24 hours after application of finish materials, maintain
temperature at 45 deg F (13 deg C) minimum and protect from
exposure to rain and moisture.
PART 2 - GENERAL
MANUFACTURER
Subject to compliance with requirements, provide products
manufactured or supplied by United States Gypsum Company, unless
otherwise indicated.
STEEL FRAMING MATERIALS
*****************************************************************
FRAMING IS ALSO AVAILABLE IN SOME AREAS WITH ALUMINIZED FINISH
PER ASTM A 463 OR WITH AN ALUMINUM-ZINC ALLOY COATING, PER ASTM A
792.
*****************************************************************
Steel Framing - General: Uncoated steel thickness shall comply
with ASTM A 568. Hot-dipped galvanize to comply with ASTM A 525
G60. Fabricate to comply with ASTM C 645.
*****************************************************************
SHOW RUNNER AND STUD DEPTH, TYPE, AND GAGE ON DRAWINGS OR SPECIFY
IN PARAGRAPHS BELOW.
*****************************************************************
Runners: Unimast Types CR and UR, 33 ksi minimum yield strength,
gage as shown on drawings, depth to match studs.
Studs: Size and gage as shown on drawings; provide following
types:
Unimast Type SJ, 40 ksi minimum yield strength.
Unimast Type ST, 33 ksi minimum yield strength.
Steel Framing Fasteners: Type S-12 self-drilling screws, 1/2
inch long pan head type or 5/8 inch long low profile head type
with CLIMASEAL corrosion resistant finish.
Anchors: Provide types required to securely attach framing to
adjacent construction.
*****************************************************************
FOLLOWING ARE EXAMPLES ONLY. SPECIFY FASTENERS SUITABLE FOR
CONDITIONS OF USE.
*****************************************************************
Concrete: 5/32 inch diameter low-velocity power-driven fastener
with 1-1/2 inches minimum penetration.
Steel: Self-drilling screws.
Plywood Subfloor and Steel Joist Framing: Type S-12 pilot-point
screws, 1-15/16 inches long.
Curtain Wall Clip: Unimast Curtain Wall Slide Clip.
Framing Accessories: Provide bracing, blocking, metal angles,
and other accessories as shown on drawings and as required for
application intended.
CEMENT BOARD MATERIALS
*****************************************************************
DUROCK EXTERIOR CEMENT BOARD CAN ALSO BE USED AS AN INTERIOR TILE
BACKER BOARD, SEE USG PRODUCT FOLDER SA-932.
*****************************************************************
Cement Board: DUROCK Exterior Cement Board; aggregated portland
cement board with polymer-coated, woven glass-fiber mesh embedded
in front and back surfaces.
Thickness: 1/2 inch minimum.
Size: 4 feet wide x 8 feet long.
Faces: Smooth on one side, coarse on other side.
Edges: Formed, smooth, reinforced edges; square
cut ends.
Weight:3 pounds per square foot maximum.
Flexural Strength: 1000 psi minimum per ASTM C 947.
Water Absorption: 10% by weight max., 24 hr. per
ASTM C 948.
Nail Pull Resistance: 125 lbs. min., 0.4 inch head diameter, wet
or dry, per ASTM C 473.
Freeze/Thaw: 100 cycles with no deterioration per ASTM C 666
Procedure A.
Flame Spread, Smoke Developed: 5, 0 per ASTM E 84.
Cement Board Fasteners: DUROCK Screws, wafer head, self-drilling
screw with CLIMASEAL corrosion resistant finish.
Metal Framing: Type S-12, 1-1/4 inches or 1-5/8
inches.
Use 1-5/8 inches fasteners when cement board is installed over
1/2 inch maximum rigid foam insulation.
Wood Framing: Type S, 1-5/8 inches.
Joint Reinforcement: As follows:
Reinforcing Tape: DUROCK Exterior Tape, 2 inches wide, polymer
coated woven glass-fiber mesh with pressure-sensitive adhesive on
one side.
Joint Compound: DUROCK Exterior Basecoat; ready-to-mix portland
cement mortar containing dry latex polymers; gray.
Surface Control Joint: SHEETROCK Zinc Control Joint No. 093,
roll-formed zinc.
Trim Accessories: DUROCK corner beads and 1/2 inch trim angles;
zinc alloy.
Water Barrier: TYVEK HOUSEWRAP, high density polyethylene fiber
water and air barrier, manufactured by E.I. duPont de Nemours &
Company.
*****************************************************************
NO. 15 ASPHALT FELT CAN BE SPECIFIED INSTEAD OF TYVEK.
*****************************************************************
Staples: 1/2 inch crown, 3/8 inch leg; galvanized.
INSULATION
*****************************************************************
SHOW INSULATION THICKNESS OR R-VALUE ON DRAWINGS OR SPECIFY
BELOW. INSULATION CONSIDERATIONS INCLUDE THERMAL REQUIREMENTS,
VAPOR RETARDER REQUIREMENTS, FIRE PERFORMANCE CHARACTERISTICS,
AND CONDITIONS OF USE.
*****************************************************************
Blanket Insulation: THERMAFIBER Mineral Fiber Insulation,
thickness or R-value as shown on drawings.
THERMAFIBER Sound Attenuation Fire Blankets (SAFB); ASTM C 665,
Type I; 15 flame spread, 0 smoke developed.
THERMAFIBER Fire Safety FS-15 Insulating Blankets; ASTM C 665,
Type I; 15 flame spread, 0 smoke developed.
THERMAFIBER Fire Safety FS-25 Insulating Blankets, foil faced;
ASTM C 665, Type III; 25 flame spread, 5 smoke developed.
THERMAFIBER Aluminum Foil-Faced Blankets, foil faced vapor
retarder with nailing flanges; ASTM C 665, Type III.
Fire Safing Insulation: THERMAFIBER Safing Insulation and steel
safing clips.
*****************************************************************
RIGID INSULATION MAY BE REQUIRED WHEN USING DUROCK EXTERIOR
FINISH TO HELP CONTROL POTENTIAL "SHADOWING" ON SURFACE OF WALL
DUE TO CONDENSATION. SPECIFY TYPE OF RIGID FOAM INSULATION
REQUIRED. DO NOT USE EXPANDED POLYSTYRENE (EPS OR "BEAD BOARD")
OR EXCEED 1/2 INCH THICKNESS.
*****************************************************************
EXTERIOR FINISH MATERIALS
*****************************************************************
INCLUDE THIS ARTICLE FOR DUROCK EXTERIOR FINISH, A STUCCO-LOOK,
WEATHER RESISTANT, TEXTURED COATING.
*****************************************************************
Base Coat: DUROCK Exterior Basecoat; ready-to-mix portland
cement mortar containing dry latex polymers; gray.
Textured Coating: DUROCK Exterior Finish; acrylic coating, ready
mixed; fine or coarse formulation and color as selected from
manufacturer's standards.
Mixing: Mix in accordance with manufacturer's instructions.
Water shall be clean and potable.
SETTING AND GROUTING MATERIALS
*****************************************************************
INCLUDE THIS ARTICLE IF CERAMIC TILE OR THIN BRICK VENEER
FINISHES ARE USED. WHITE MORTAR AND GROUT ARE ALSO AVAILABLE.
*****************************************************************
Skim Coat and Mortar: DUROCK or DURABOND Latex Fortified Mortar;
ready-to-mix, thin-set mortar containing dry latex polymers,
especially formulated for use with DUROCK Exterior Cement Board;
gray or white.
Grout: DUROCK Latex Fortified Grout; ready-to-mix grout
containing dry latex polymers, especially formulated for use with
DUROCK Exterior Cement Board; gray or white.
Mixing: Mix in accordance with manufacturer's instructions.
Water shall be clean and potable.
*****************************************************************
SPECIFICATIONS FOR TILE, THIN BRICK, AGGREGATE COATING, OR OTHER
FINISH MATERIALS CAN BE INSERTED HERE. COORDINATE WITH WORK
SPECIFIED IN OTHER SECTIONS.
*****************************************************************
PART 3 - EXECUTION
GENERAL
Comply with manufacturer's printed installation instructions for
products and applications indicated, except where more stringent
requirements apply.
*****************************************************************
RETAIN BELOW IF RATED CONSTRUCTION IS REQUIRED.
*****************************************************************
Conform to construction requirements of tested assemblies used to
demonstrate required fire resistance.
EXAMINATION
Coordinate work of this section with building structural system;
ensure anchorage provisions have been installed to receive cement
board system.
*****************************************************************
RETAIN BELOW IF WOOD OR METAL FRAMING ARE SPECIFIED IN ANOTHER
SECTION.
*****************************************************************
Examine framing for compliance with requirements and conditions
affecting work of this section. Do not proceed with installation
until unsatisfactory conditions have been corrected.
STEEL FRAMING INSTALLATION
*****************************************************************
SPACING FOR RUNNER ATTACHMENT AND STUDS SHOULD BE SHOWN ON
DRAWINGS OR SPECIFIED BELOW. SPACING SHOULD BE DETERMINED BY
ARCHITECT OR ENGINEER IN ACCORDANCE WITH GUIDELINES CONTAINED IN
USG PRODUCT LITERATURE. WHERE REQUIRED BY POTENTIAL DEFLECTION
OF BUILDING STRUCTURE, INDICATE ADDITIONAL REQUIREMENTS TO ALLOW
FOR "FLOATING" CONSTRUCTION OF EXTERIOR WALLS.
*****************************************************************
Runners: Accurately align and secure to base and head with power
driven fasteners spaced as shown on drawings.
Studs: Position vertically in runners at spacing shown on
drawings. Anchor each stud to runner with four screws, two at top
and two at bottom, with one screw in each flange.
At building control joints that extend through wall, provide
breaks in top and bottom runner track. Install 1-1/2 inch cold-
rolled channel alignment stabilizers spaced maximum 5 feet o.c.
vertically. Place channels through holes in stud web of the first
two adjacent studs on both sides of the joint, and securely
attached to the first adjacent stud on either side
of the joint.
*****************************************************************
SHOW DETAILS OF PENETRATIONS ON DRAWINGS.
*****************************************************************
At wall penetrations such as windows and doors, provide
additional reinforcement at header, sill, and jambs to transfer
and support loads.
Provide framing accessories and curtain wall clips as shown and
drawings and as required for conditions of use.
RIGID FOAM INSULATION
Install rigid foam insulation over framing with fasteners
adequate to hold in place until covered by cement boards. Butt
ends and edges and stagger joints.
WATER BARRIER
Install water barrier in shingle-like manner beginning at bottom
of
wall. Overlap edges 2 inches.
CEMENT BOARD
Apply cement board panels with coarse side towards exterior and
with ends over supports. Stagger end joints in successive
courses. Fit ends and edges closely, but not forced
together.
Fasten cement board panels to framing with specified fasteners.
Space 8 inches o.c. at walls, 6 inches o.c. at soffits. Drive
fasteners in field of panels first, working towards ends and
edges. Hold panel in firm contact with framing while driving
fasteners. Locate perimeter fasteners at least 3/8 inch from ends
and edges. Drive screws so heads are flush with surface of
panels. Provide firm panel contact with framing.
Reinforcing Tape: Apply over joints and corners except where
corner beads or control joints are used. Do not
overlap.
*****************************************************************
USE TRIM ACCESSORIES WITH DUROCK EXTERIOR FINISH AND, IF
REQUIRED, WITH AGGREGATE COATING. OPTIONAL TRIM ANGLES CAN BE
USED AT PERIMETER OF CEMENT BOARD PANEL SYSTEM.
*****************************************************************
Trim Accessories: Install corner beads at outside corners.
Install trim angles where shown on drawings. Fasten with
staples.
Vent soffits as shown on drawings.
EXPANSION AND CONTRACTION
Provide surface control joints where shown on drawings and as
follows:
*****************************************************************
ADJUST LISTING BELOW TO PROJECT.
*****************************************************************
Wall abuts a structural element or dissimilar wall
or surface.
Construction changes within the plane of the wall.
At control or expansion joints in underlaying construction.
20 feet o.c. maximum for DUROCK Exterior Finish system; 16 feet
o.c. maximum for tile and thin brick finishes.
Separate cement boards behind control joints. Where vertical and
horizontal control joints intersect, vertical control joints
shall be continuous and horizontal control joints shall abut.
Apply sealant to splices, terminals, and intersections of control
joints as specified in Division 7 Section "Joint
Sealers".
BLANKET AND SAFING INSULATION
Blanket Insulation: Install to completely fill stud cavity to
thickness required. Tightly butt ends and sides of blankets.
Staple nailing flanges to sides of wood studs and plates, do not
attach to face of framing.
*****************************************************************
RETAIN ABOVE WITH USING WOOD FRAMING AND INSULATION BLANKETS WITH
NAILING FLANGES.
RETAIN BELOW IF USING INSULATION BLANKETS WITH VAPOR RETARDER.
*****************************************************************
Install vapor retarder towards the predominately warm, humid side
of the exterior wall.
Safing Insulation: Install at perimeter of fire rated floor
slabs and where shown on drawings. Secure with safing clips
spaced 24 inches o.c. maximum.
*****************************************************************
RETAIN FOLLOWING IF EXTERIOR FINISH SYSTEM IS REQUIRED.
*****************************************************************
EXTERIOR FINISH SYSTEM
Surfaces to receive exterior finish shall be clean and dry prior
to application.
Joints: Apply base coat material over reinforcing tape and trim
accessories and flush with adjacent cement board. Force base
coat through tape to fill and level joints, or prefill joints and
then tape and level joints. Allow to set 24 hours before
application of base coat.
Base Coat: Apply 1/16 inch minimum thick base coat over entire
surface. Base coat shall be uniform, smooth, and flat. Allow to
set 24 hours before application of exterior finish.
Textured Coating: Provide 1/16 inch minimum, 3/16 inch maximum
coating thickness in specified texture.
*****************************************************************
SPECIFY REQUIRED TEXTURE BELOW.
*****************************************************************
Lace Finish: Trowel on a first coat. Before surface moisture
leaves, skip-trowel on second coat with trowel held
flat.
Spanish Finish: Trowel on a smooth first coat. Apply a second
coat using random, overlapping trowel strokes.
Sandstone Finish: Trowel on a first coat and immediately double
back with a second coat. Using a sponge float, press surface to
achieve required texture.
Float Finish: Trowel on finish and immediately double back with
a second coat. Rub surface with a wood float using a uniform,
circular motion to bring sand particles up to the
surface.
*****************************************************************
RETAIN FOLLOWING IF TILE OR THIN BRICK VENEER IS REQUIRED.
CHANGE "TILE" TO "THIN BRICK" BELOW AS REQUIRED.
*****************************************************************
TILE OR THIN BRICK VENEER
Comply with applicable requirements of Division 4 Section "Unit
Masonry".
*****************************************************************
RETAIN ABOVE FOR THIN BRICK OR BELOW FOR TILE. IF RELATED
SECTION IS NOT INCLUDED IN PROJECT MANUAL, IT MAY BE NECESSARY TO
EXPAND THIS SECTION TO SPECIFY ADDITIONAL REQUIREMENTS.
*****************************************************************
Comply with applicable requirements of Division 9
Section "Tile".
Skim Coat: Apply uniform 1/8 inch minimum thick coat of mortar
over cement board. Surface shall be smooth and flat. Allow to
set 24 hours before application of tile or thin brick.
Installation: Comply with ANSI A108.5 requirements for thin-set
installation. Use notched trowel of size required by thickness
of tile or thin brick. Apply uniform setting bed to skim coated
surface. Back-butter tile or thin brick and firmly press into
freshly applied mortar; use sliding and twisting motion to embed
units and obtain complete mortar contact. Allow mortar to set
for 24 hours before application of grout.
Grout: Comply with ANSI A108.10 and TCA Handbook for Ceramic
Tile Installation. Force maximum amount of grout into joints and
tool grout into joints to provide neat and uniform appearance.
Clean grout from finished surfaces. Cure grout as
required.
*****************************************************************
RETAIN FOLLOWING IF AGGREGATE COATING IS REQUIRED.
*****************************************************************
AGGREGATE COATING
Apply to taped exterior cement board surface as specified in
Division 9 Section "Aggregate Coatings".
SEALANTS
Apply sealants around perimeter of and penetrations through
cement board building panel systems as specified in Division 7
Section "Joint Sealers".
END OF SECTION 07480
*****************************************************************
Copyright 1991 by U.S. Gypsum Co.
A limited license is extended to qualified design professionals
to duplicate and print this guide specification for the purpose
of incorporating products manufactured by U.S. Gypsum Co. into a
construction specification or purchase order.
Notice: We shall not be liable for incidental and consequential
damages, directly or indirectly sustained, nor for any loss
caused by application of these goods not in accordance with